სხივის დეტექტორი,FIREBEAM BL Beam Detector
Please sign in so that we can notify you about a reply
Electrical Specifications: | |
---|---|
Supply Voltage | 12 to 30 Vdc normal |
Supply Current | 5.5mA in all operational states |
Supply Current | 13.5mA in fast commissioning |
Environmental Specifications: | |
Temperature | -10°C to +55°C |
Humidity | 10 to 95% RH Non-condensing |
Protection Index | IP65 when suitably mounted and terminated |
Mechanical Specifications: | |
Beam Head | H:180mm x W:155mm x D:137mm - Weight 1.1kg |
70KIT140 Mid-Range Reflector | H:293mm x W:293mm x D:5mm - Weight 0.8kg |
140KIT160 Long-Range Reflector | H:394mm x W:394mm x D:5mm - Weight 1.8kg |
Adapter | H:270mm x W:250mm x D:5mm - Weight 0.6Kg (mounts the Beam Head onto Unistrut) |
Optical Specifications: | |
Optical Wavelength | 870nm |
Maximum Angular Alignment | ±5° |
Maximum Angular Misalignment | (static not auto-aligning) Beam Head ±0.4° / Reflector ±2° |
Operational Specifications: | |
Protection Range | |
Fire Beam BLUE | Standard Product 7 to 70 metres. Use short range mask for distances between 7 & 20 metres |
70KIT140 | Mid-Range Reflector Kit 70 to 140 metres |
140KIT160 | Long Range Reflector Kit 140 to 160 metres |
Alarm Sensitivity Levels | |
25% (1.25dB) to 50% (3dB) in 1% (0.05dB) increments (default 35% (1.87dB)) | |
Alarm Condition: | |
Obscuration drops to below pre-defined sensitivity level. | |
Time to Alarm Condition adjustable between 2 to 30 seconds in 1 second increments (default 10 seconds) | |
Alarm Indication: | |
App Status - FIRE | |
Head Red Flashing LED | |
Alarm Relay Change Over (CO) Contact | |
Rating 2A @ 30 VDC | |
Test / Reset Features: | |
Beam test function with App | |
Alarm latching / auto-reset selectable (default auto-reset) | |
Alarm reset in latching mode with App reset function, removing power for >5 seconds or momentarily apply >5 VDC to reset connections in Beam Head | |
Fault Sensitivity Level: | |
<4>#/td### | |
Fault Condition: | |
Obscuration drops to below the fault sensitivity level within 1 second | |
Power Down or Supply Voltage < 9 VDC | |
Commissioning modes, Pre-Alignment and Auto-Alignment | |
Beam turned off during Beam Maintenance | |
Time to Fault Condition adjustable, 2 to 60 seconds in 1 second increments (default 10 seconds) | |
Fault Indication: | |
App Status - FAULT | |
Head Yellow Flashing LED 1 Second | |
Fault Relay Change Over (CO) Contact Rating 2A @ 30 VDC | |
Normal Condition: | |
Obscuration level is above the Alarm sensitivity level | |
App Status - NORMAL | |
Programmable on/off | |
Head Green Flashing LED | |
Programmable on/off | |
Auto-Align / Beam Contamination Compensation: | |
Auto-align during normal operation if obscuration drops below 90% for the duration of the align time set (doesn't affect normal operating mode) | |
Beam Contamination Compensation 4 hour monitoring. Compensation data available in the App |