The Fire Beam Xtra self-aligns to the centre of the reflector during commissioning and will automatically keep alignment when building movement occurs. This intelligent motorisation will result in fewer false alarms, thereby saving time, resources –and, ultimately– money.

Stock in stores
  • Tbilisi - Out of stock
  • Batumi - Out of stock
Our advantages
Delivery
Payment options
Electrical Specifications:
Supply Voltage12 to 30 Vdc normal
Supply Current5.5mA in all operational states
Supply Current13.5mA in fast commissioning
Environmental Specifications:
Temperature-10°C to +55°C
Humidity10 to 95% RH Non-condensing
Protection IndexIP65 when suitably mounted and terminated
Mechanical Specifications:
Beam HeadH:180mm x W:155mm x D:137mm - Weight 1.1kg
70KIT140 Mid-Range ReflectorH:293mm x W:293mm x D:5mm - Weight 0.8kg
140KIT160 Long-Range ReflectorH:394mm x W:394mm x D:5mm - Weight 1.8kg
AdapterH:270mm x W:250mm x D:5mm - Weight 0.6Kg (mounts the Beam Head onto Unistrut)
Optical Specifications:
Optical Wavelength870nm
Maximum Angular Alignment±5°
Maximum Angular Misalignment(static not auto-aligning) Beam Head ±0.4°  /  Reflector ±2°
Operational Specifications:
Protection Range
Fire Beam BLUEStandard Product 7 to 70 metres. Use short range mask for distances between 7 & 20 metres
70KIT140Mid-Range Reflector Kit 70 to 140 metres
140KIT160Long Range Reflector Kit 140 to 160 metres
Alarm Sensitivity Levels
25% (1.25dB) to 50% (3dB) in 1% (0.05dB) increments (default 35% (1.87dB))
Alarm Condition:
Obscuration drops to below pre-defined sensitivity level.
Time to Alarm Condition adjustable between 2 to 30 seconds in 1 second increments (default 10 seconds)
Alarm Indication:
App Status - FIRE
Head Red Flashing LED
Alarm Relay Change Over (CO) Contact
Rating 2A @ 30 VDC
Test / Reset Features:
Beam test function with App
Alarm latching / auto-reset selectable (default auto-reset)
Alarm reset in latching mode with App reset function, removing power for >5 seconds or momentarily apply >5 VDC to reset connections in Beam Head
Fault Sensitivity Level:
<4>#/td###
Fault Condition:
Obscuration drops to below the fault sensitivity level within 1 second
Power Down or Supply Voltage < 9 VDC
Commissioning modes, Pre-Alignment and Auto-Alignment
Beam turned off during Beam Maintenance
Time to Fault Condition adjustable, 2 to 60 seconds in 1 second increments (default 10 seconds)
Fault Indication:
App Status - FAULT
Head Yellow Flashing LED 1 Second
Fault Relay Change Over (CO) Contact Rating 2A @ 30 VDC
Normal Condition:
Obscuration level is above the Alarm sensitivity level
App Status - NORMAL
Programmable on/off
Head Green Flashing LED
Programmable on/off
Auto-Align / Beam Contamination Compensation:
Auto-align during normal operation if obscuration drops below 90% for the duration of the align time set (doesn't affect normal operating mode)
Beam Contamination Compensation 4 hour monitoring. Compensation data available in the App